UK IRE Ventilation Catalogue 25 - Flipbook - Page 11
VENTILATION
VENTILATION INDEX
AHU connection kit MAH3M for ECOi and ECO G
CONEX Bluetooth®
control built-in.
CZ-RTC6BL
5 HP
Model
PAW-
10 HP
20 HP
30 HP
40 HP
50 HP
60 HP
70 HP
80 HP
160MAH3M 280MAH3M 560MAH3M 280MAH3M 560MAH3M 560MAH3M 560MAH3M 560MAH3M 560MAH3M
560MAH3M 560MAH3M 560MAH3M 560MAH3M 560MAH3M 560MAH3M
280MAH3M 560MAH3M 560MAH3M 560MAH3M
280MAH3M 560MAH3M
Cooling capacity
kW
14,0
28,0
56,0
84,0
112,0
140,0
168,0
196,0
224,0
Heating capacity
kW
16,0
31,5
63,0
95,0
127,0
155,0
189,0
219,0
252,0
m³/h
1 140 / 2 598
3 498 / 4 998
0,9
0,9
0,9
0,9
0,9
0,9
0,9
0,9
0,9
mm
500 x 400
x 150
500 x 400
x 150
500 x 400
x 150
500 x 400
x 150*
500 x 400
x 150*
500 x 400
x 150*
500 x 400
x 150*
500 x 400
x 150*
500 x 400
x 150*
Air flow
Cool Min / Max
Bypass factor recommended
Dimension
HxWxD
7002 / 10002 10500/15000 13998/19998 17496/24996 21000/30000 35000/24000 40000/28000
Net weight
kg
11,5
11,5
11,5
11,5*
11,5*
11,5*
11,5*
11,5*
11,5*
Pipe length range
m
10 ~ 100
10 ~ 100
10 ~ 100
10 ~ 100
10 ~ 100
10 ~ 100
10 ~ 100
10 ~ 100
10 ~ 100
Elevation difference (in / out) Max
Piping diameter
Intake temperature of AHU
connection kit
Ambient temperature of
outdoor unit
10
10
10
10
10
10
10
10
10
Liquid
m
Inch (mm)
3/8 (9,52)
3/8 (9,52)
5/8 (15,88)
3/4 (19,05)
3/4 (19,05)
3/4 (19,05)
3/4 (19,05)
7/8 (22,22)
7/8 (22,22)
Gas
Inch (mm)
5/8 (15,88)
7/8 (22,22)
1 1/8 (28,58) 1 1/4 (31,75) 1 1/2 (38,15) 1 1/2 (38,15) 1 1/2 (38,15) 1 5/8 (41,28) 1 3/4 (44,45)
Cool Min ~ Max
°C DB
+18 ~ +32
+18 ~ +32
+18 ~ +32
+18 ~ +32
+18 ~ +32
+18 ~ +32
+18 ~ +32
+18 ~ +32
+18 ~ +32
Cool Min ~ Max
°C WB
+13 ~ +23
+13 ~ +23
+13 ~ +23
+13 ~ +23
+13 ~ +23
+13 ~ +23
+13 ~ +23
+13 ~ +23
+13 ~ +23
Heat Min ~ Max
°C
+16 ~ +30
+16 ~ +30
+16 ~ +30
+16 ~ +30
+16 ~ +30
+16 ~ +30
+16 ~ +30
+16 ~ +30
+16 ~ +30
Cool Min ~ Max
°C
-10 ~ +43
-10 ~ +43
-10 ~ +43
-10 ~ +43
-10 ~ +43
-10 ~ +43
-10 ~ +43
-10 ~ +43
-10 ~ +43
Heat Min ~ Max
°C
-20 ~ +15
-20 ~ +15
-20 ~ +15
-20 ~ +15
-20 ~ +15
-20 ~ +15
-20 ~ +15
-20 ~ +15
-20 ~ +15
* The value applies to one unit of the AHU connection kit.
AHU connection kit / system combination
Capacity
ECOi Series
5 HP
16 kW
Mini ECOi / ECOi EX ME2 Series
U-8LZ2E8/U-10LZ2E8/
10 HP
28 kW
U-8LE1E8/U-10LE1E8/
—
—
U-10ME2E8
20 HP
56 kW
U-20ME2E8
—
—
30 HP
84 kW
U-16ME2E8
U-14ME2E8
—
40 HP
112 kW
U-20ME2E8
U-20ME2E8
—
50 HP
140 kW
U-18ME2E8
U-16ME2E8 U-16ME2E8
60 HP
168 kW
U-20ME2E8
U-20ME2E8 U-20ME2E8
70 HP
196 kW
U-20ME2E8
U-20ME2E8 U-20ME2E8
80 HP
224 kW
U-20ME2E8
U-20ME2E8 U-20ME2E8
160MAH3M
AHU kit
—
—
—
Capacity
5 HP
16 kW
ECO G Series
All ECO G
AHU kit
160MAH3M
280MAH3M
—
—
—
10 HP
28 kW
All ECO G
280MAH3M
560MAH3M
560MAH3M
560MAH3M
560MAH3M
560MAH3M
560MAH3M
560MAH3M
—
280MAH3M
560MAH3M
560MAH3M
560MAH3M
560MAH3M
560MAH3M
—
—
—
280MAH3M
560MAH3M
560MAH3M
560MAH3M
—
—
—
—
—
280MAH3M
560MAH3M
20 HP
56 kW
U-20GE3E5
560MAH3M
Technical focus
· Maximum capacity / system: 80 HP (224 kW)
· Maximum piping length: 100 m (120 m equivalent)
· Elevation difference (indoor unit / indoor unit): 4 m
· In / out capacity ratio: 50~100%
· Maximum number of AHU connection kits: 4 units*
· Outdoor temperature range in heating: -20 ~ +15 °C
· Available temperature range for the suction air at AHU
connection kit: cool: +18 ~ +32 °C / heat: +16 ~ +30 °C
· The systems is controlled by the suction air (or room
return air) temperature (same as standard indoor unit)
· The discharge air temperature is also controlled to
prevent too-low air discharge in cooling or too-high air
discharge in heating (in case of VRF)
· Demand control (forcible thermostat-OFF control by
operating current)
· Defrost operation signal, Thermo-ON / OFF states output
· Drain pump control (drain pump and the float switch to be
supplied in local)
· External target temperature setting via indoor / outdoor
signal interface is available with CZ-CAPBC2 (Ex. 0-10 V)
· Demand control 40% to 120% (5% steps) by 0-10 V input
signal
· Connectable with S-Link system. Special care for
electrical noise may be necessary depending on the
on-site system
· Fan control signal from the PCB can be used to control
the air flow (high / mid / low and LL for Th-OFF). Need to
change the fan control circuit wiring at field
* To be simultaneous operation controlled by one remote controller sensor.
2
1
3
4
9
8
5
6
7
10
System and regulations. System overview.
1 | AHU Unit equipment (field supplied)
2 | AHU Unit system controller (field
supplied)
3 | AHU connection kit controller box (with
control PCB)
4 | Thermistor for discharge air
5 | Electronic expansion valve
6 | Thermistor for gas pipe (E3)
7 | Thermistor for liquid pipe (E1)
8 | Thermistor for suction air
9 | Inter-unit wiring
10 | ECOi or ECOi G outdoor unit
Optional controller.
Timer remote controller.
CZ-RTC5B.
11