UK RAC GEN 24 Interactive - Flipbook - Page 85
WIRING DIAGRAMS
WIRING DIAGRAMS INDEX
Floor console kits 1x1.
Indoor unit
Outdoor unit
3
2
1
Connection cable
1
2
3
L N
Infrared remote
controller (included
in the delivery)
Single phase
Power supply
230 V / 50 Hz
Floor console · R32
Indoor unit
Power supply
Recommended fuse
Power supply cable
Connection indoor / outdoor
Outdoor unit
CS-Z25UFEAW
230 V (outdoor)
16 A
3 x 1,5 mm²
4 x 1,5 mm²
CU-Z25UBEA
CS-Z35UFEAW
230 V (outdoor)
16 A
3 x 1,5 mm²
4 x 1,5 mm²
CU-Z35UBEA
CS-Z50UFEAW
230 V (outdoor)
16 A
3 x 2,5 mm²
4 x 2,5 mm²
CU-Z50UBEA
Low static pressure hide‑away kits 1x1.
Indoor unit
Outdoor unit
3
2
1
Connection cable
1
2
3
CN-DISP
1
4
CZ‑RD52CP
Included wired
remote controller
L N
Single phase
Power supply
230 V / 50 Hz
Low static pressure hide‑away · R32
Indoor unit
Power supply
Recommended fuse
Power supply cable
Connection indoor / outdoor
Outdoor unit
CS-Z25UD3EAW
230 V (outdoor)
16 A
3 x 1,5 mm²
4 x 1,5 mm²
CU-Z25UBEA
CS-Z35UD3EAW
230 V (outdoor)
16 A
3 x 1,5 mm²
4 x 1,5 mm²
CU-Z35UBEA
CS-Z50UD3EAW
230 V (outdoor)
16 A
3 x 2,5 mm²
4 x 1,5 mm²
CU-Z50UBEA
CS-Z60UD3EAW
230 V (outdoor)
16 A
3 x 2,5 mm²
4 x 1,5 mm²
CU-Z60UBEA
85