UK VENTILATION GEN 26 - Flipbook - Page 13
RANGE
R410
VENTILATION
AHU connection kit MAH4M for ECOi 2-Pipe combination
from 22 to 34 HP · R410A
Built-in controller.
AHU kit PAW-P+100MAH4M
22 HP
24 HP
26 HP
28 HP
30 HP
32 HP
34 HP
AHU connection kit
156EEVPACK
174EEVPACK
174EEVPACK
174EEVPACK
174EEVPACK
174EEVPACK
174EEVPACK
Outdoor unit
U-10ME2E8 +
U-12ME2E8
2×U-12ME2E8
U-10ME2E8 +
U-16ME2E8
U-12ME2E8 +
U-16ME2E8
U-14ME2E8 +
U-16ME2E8
2×U-16ME2E8
U-14ME2E8 +
U-20ME2E8
14+20
Multi combination
10+12
12+12
10+16
12+16
14+16
16+16
Nominal cooling capacity
kW
61,5
68,0
73,0
78,5
85,0
90,0
96,0
Nominal heating capacity
kW
69,0
76,5
81,5
87,5
95,0
100,0
108,0
Minimum cooling continuous 1)
kW
15,3
21,5
21,5
21,5
21,5
21,5
21,5
Minimum heating continuous 2)
kW
17,5
24,7
24,7
24,7
24,7
24,7
24,7
m³/h
6 000
6 000
6 000
6 000
7 000
7 000
8 500
30 000
Air flow volume
Min
Max
m³/h
24 000
24 000
24 000
25 000
25 000
25 000
AHU DX coil heat
exchanger volume
Min
dm³
5,0
6,0
6,0
6,0
6,0
6,0
7,0
Max
dm³
27,0
34,0
27,0
34,0
34,0
34,0
36,0
Piping length
Min / Max
m
10 / 100
10 / 100
10 / 100
10 / 100
10 / 100
10 / 100
10 / 100
Maximum branch pipe length
m
12
12
12
12
12
12
12
Maximum pipe length difference after
1st joint
m
10
10
10
10
10
10
10
Maximum elevation difference (in / out) m
10
10
10
10
10
10
10
Piping connections EEV
16
7/8"
7/8"
7/8"
7/8"
7/8"
7/8"
Piping diameter
branch pipe
On coil temperature
Outdoor temperature
mm
Liquid
Inch (mm)
5/8 (15,88)
5/8 (15,88)
3/4 (19,05)
3/4 (19,05)
3/4 (19,05)
3/4 (19,05)
3/4 (19,05)
Gas
Inch (mm)
1 1/8 (28,58)
1 1/8 (28,58)
1 1/4 (31,75)
1 1/4 (31,75)
1 1/4 (31,75)
1 1/4 (31,75)
1 1/4 (31,75)
°C DB
12 / 32
12 / 32
12 / 32
12 / 32
12 / 32
12 / 32
12 / 32
°C WB
8 / 25
8 / 25
8 / 25
8 / 25
8 / 25
8 / 25
8 / 25
Heat Min ~ Max °C DB
0 / 32 3)
0 / 32 3)
0 / 32 3)
0 / 32 3)
0 / 32 3)
0 / 32 3)
0 / 32 3)
Cool Min ~ Max
°C DB
‑10 / 46
‑10 / 46
‑10 / 46
‑10 / 46
‑10 / 46
‑10 / 46
‑10 / 46
Heat Min ~ Max °C WB
‑25 / 18
‑25 / 18
‑25 / 18
‑25 / 18
‑25 / 18
‑25 / 18
‑25 / 18
Cool Min ~ Max
1) At rated condition with 35 °C DB outdoor and 27 °C DB / 19 °C WB on coil. 2) At rated condition with 7 °C DB / 6 °C WB outdoor and 20°C DB on coil. 3) In case of on coil temperature of 5 °C or below and of
31 °C and above air flow would be restricted.
Accessories
Accessories
PAW-P+102SENSPACK
AHU connection kit sensor pack 1 (2 pcs of SENSOR
PT1000 HT IP67 ‑50/250 CABLE 6 m PCK)
PAW-P+156EEVPACK
EEV pack 4 (1 pc of expansion valve ≤ 61,5 kW (R32 /
R410A) and 1 pc of UNIPOLAR stator and filter strainers)
PAW-P+116EEVPACK
EEV pack 1 (1 pc of expansion valve ≤ 16,0 kW (R32 /
R410A) and 1 pc of UNIPOLAR stator and filter strainers)
PAW-P+174EEVPACK
EEV pack 5 (1 pc of expansion valve ≤ 96,0 kW (R32 /
R410A) and 1 pc of UNIPOLAR stator and filter strainers)
PAW-P+133EEVPACK
EEV pack 2 (1 pc of expansion valve ≤ 33,0 kW (R32 /
R410A) and 1 pc of UNIPOLAR stator and filter strainers)
PAW-P+145EEVPACK
EEV pack 3 (1 pc of expansion valve ≤ 45,0 kW (R32 /
R410A) and 1 pc of UNIPOLAR stator and filter strainers)
Remote control pack (1 pc of PGNE 132 x 64 mm,
PAW-P+100PGNEPACK mounting panel and 1 pc of cable L= 1,5 m, telephone
connectors)
13