UK VENTILATION GEN 26 - Flipbook - Page 21
RANGE
NEW
NEW! Air curtain with DX coil, connected to ECOi 2-Pipe
· Advanced defrost control without disrupting the air
curtain effect or causing cold drafts
· Flexible installation: suspended as standard, cassette or
built‑in optional
· Quiet operation
Touch screen
remote
controller*.
Air outlet height 2,8 m
*Includes two remote controllers: a touch screen remote controller and an intelligent built-in
controller for setup.
PAW-M2-100R
PAW-M2-150R
PAW-M2-200R
PAW-M2-250R
4 HP
5 HP
8 HP
10 HP
7,6
12,0
16,3
20,5
Outdoor unit minimum size
Cooling capacity 1)
Heating capacity
Max
VENTILATION
kW
Max
kW
9,4
15,0
20,7
25,6
Air flow
High
m³/h
1 800
2 700
3 600
4 500
Heat Exchanger
Volume
L
1,60
2,80
3,90
5,10
Electric consumption fan
230 V / 50 Hz
kW
0,33
0,50
0,66
0,83
Current
230 V / 50 Hz
A
2,40
3,60
4,80
6,00
Sound pressure
2)
3)
Dimension
Max
dB(A)
56
57
58
59
H x W x D (x D 4))
mm
300 x 1 000 x 750 (x 890)
300 x 1 500 x 750 (x 890)
300 x 2 000 x 750 (x 890)
300 x 2 500 x 750 (x 890)
kg
61
74
96
138
Net weight
Fan type
Piping diameter 5)
Liquid / Gas
Door width
Inch (mm)
EC
EC
EC
EC
1/4 (6,35) / 1/2 (12,70)
3/8 (9,52) / 5/8 (15,88)
3/8 (9,52) / 5/8 (15,88)
1/2 (12,70) / 7/8 (22,22)
1,0
1,5
2,0
2,5
R32 / R410A
R32 / R410A
R32 / R410A
R32 / R410A
m
Refrigerant
Tentative data
Air outlet height 3,2 m
PAW-M3-100R
PAW-M3-150R
PAW-M3-200R
PAW-M3-250R
4 HP
6 HP
10 HP
10 HP
10,0
13,8
21,7
25,2
Outdoor unit minimum size
Cooling capacity
1)
Heating capacity
2)
Max
kW
Max
kW
11,4
17,0
25,7
30,2
High
m³/h
2 400
3 200
4 900
5 700
Heat Exchanger
Volume
L
1,60
2,80
3,90
5,10
Electric consumption fan
230 V / 50 Hz
kW
0,50
0,66
0,99
1,16
Current
230 V / 50 Hz
A
3,60
4,80
7,20
8,40
Air flow
Sound pressure
3)
Dimension
Max
dB(A)
58
59
60
61
H x W x D (x D 4))
mm
300 x 1 000 x 750 (x 890)
300 x 1 500 x 750 (x 890)
300 x 2 000 x 750 (x 890)
300 x 2 500 x 750 (x 890)
kg
65
78
104
145
Net weight
Fan type
Piping diameter 5)
Liquid / Gas
Door width
Inch (mm)
EC
EC
EC
EC
3/8 (9,52) / 5/8 (15,88)
3/8 (9,52) / 5/8 (15,88)
1/2 (12,70) / 7/8 (22,22)
1/2 (12,70) / 7/8 (22,22)
m
Refrigerant
1,0
1,5
2,0
2,5
R32 / R410A
R32 / R410A
R32 / R410A
R32 / R410A
1) Minimum discharge temperature of 17 °C. With an air intake temperature of 27 °C RH 50%, evaporation temperature of 4,5 °C, SH 3 K, SC 20 K. 2) Air intake temperature of 20 °C, refrigerant R32, outside
temperature ~0 °C, condensation temperature 48 °C, SH 40 K and SC 3 K. 3) Measured in distance from 3,0 m. 4) Depth including brackets for cassette mounting and built-in models. For built-in model height
changes + 100 mm for the channels. 5) Piping diameter to outdoor unit. Air curtain port connection for all sizes is 1/2” (12,7 mm) / 7/8” (22,00 mm). For smaller models, field-supplied adapters are required to
ensure proper pipe connection.
Accessories
PAW-CDP1
Drain pump kit
Technical focus
· Advanced defrost control maintains the air curtain effect without cold drafts
· Four air curtain lengths available: P2 and P3 – 1,0 m, 1,5 m, 2,0 m, and
2,5 m
· Installation height up to 3,2 m
· Flexible installation: suspended as standard, cassette or built‑in optional*
· Includes one user‑friendly touchscreen remote controller
· Effortless settings management via touchscreen control
· Optional smart temperature control automatically adjusts to outdoor
conditions
· Integrated control with door sensor and BMS ON / OFF functionality
· Scalable setup: group up to 10 units for synchronized operation
· Drain pump optional
Installation heights and three mounting possibilities
Suspended (standard)
Maximum installation
height:
M3: 3,2 m
M2: 2,8 m
Cassette
(optional: PAW-M2100/150/200/250GVP)
Built-in
(optional: PAW-M3100/150/200/250BVP)
*Cassette type (PAW-M2-100/150/200/250GVP) or built-in type (PAW-M3-100/150/200/250BVP)
available upon request.
21