UK VENTILATION GEN 26 - Flipbook - Page 9
RANGE
VENTILATION
System example with AHU connection kit MAH4M and Mini ECOi outdoor unit.
· AHU connection kit in an IP 65 casing, contains PCBs and
terminal connections mounted inside
· Select the size of the expansion valve pack based on the
capacity
· Direct Modbus communication with a built‑in Modbus
S‑Link interface
· The heat exchanger, fan, and fan motor to be mounted in
the AHU are field‑supplied
2 options for external BMS connection
AHU connection kit +
expansion valve pack
Modbus: RS485
Other BMS: Hardwired
Mini ECOi or ECOi EX
2-Pipe outdoor unit
Air handling unit
(AHU)
Demand control on the outdoor unit managed by external 0-10 V signal.
0-10 V control
With 0‑10 V demand control, the outdoor unit capacity can be adjusted in each 5% demand step. Temperature set control
(default discharge temperature control) is also available in each 0,5 K step.
Input voltage* (V)
0
1,0
1,5
2,0
2,5
3,0
3,5
4,0
4,5
5,0
5,5
6,0
6,5
7,0
7,5
8,0
8,5
9,0
9,5
Demand (% of nominal current)
No cut 1)
40
45
50
55
60
65
70
75
80
85
90
95
100
105
110
115
120
No limit / Full capacity 2)
Indoor unit start / stop
Stop 1)
Start
1) No cut / stop: AHU system / indoor unit is completely switched OFF.
2) No limit: No restrictions applied by BMS to AHU system / indoor unit performance (equivalent to “full-load operation“ of AHU system / indoor unit).
9
10
1
2 3
8
4
11
5
6
7
System and regulations. System overview.
1 | AHU Unit equipment (field supplied)
2 | Thermistor for gas pipe (E3)
3 | Pressure transductor
4 | Thermistor for discharge air (BL)
5 | Thermistor for liquid pipe (E1)
6 | Thermistor for suction air (TA)
7 | Expansion valve (accessorie part)
8 | Fan (field supplied)
9 | AHU connection kit controller box
10 | Optional remote controller
11 | Outdoor unit Mini ECOi and 2‑Pipe ECOi EX
Optional parts for AHU connection kit MAH4M.
EEV (Electric expansion valve) pack.
EEV controls refrigerant circuit superheat (or subcooling), directly managed by the c.pCO mini controller. Different sizes based on capacity.
EEV pack 1: includes one expansion valve (≤ 16,0 kW (R32 / R410A) , one unipolar stator, and two bidirectional filters
PAW‑P+116EEVPACK
EEV pack 2: includes one expansion valve (≤ 33,0 kW (R32 / R410A) , one unipolar stator, and two bidirectional filters
PAW‑P+133EEVPACK
EEV pack 3: includes one expansion valve (≤ 45,0 kW (R32 / R410A) , one unipolar stator, and two bidirectional filters
PAW‑P+145EEVPACK
EEV pack 4: includes one expansion valve (≤ 61,5 kW (R32 / R410A) , one unipolar stator, and two bidirectional filters
PAW‑P+156EEVPACK
EEV pack 5: includes one expansion valve (≤ 96,0 kW (R32 / R410A) , one unipolar stator, and two bidirectional filters
PAW‑P+174EEVPACK
*Example image.
Remote control pack.
AHU connection kit sensor pack.
PAW‑P+100PGNEPACK.
Graphic display remote control, managing both
icons and international fonts.
PAW‑P+102SENSPACK.
AHU connection kit sensor pack 1 (2 pcs of SENSOR
PT1000 HT IP67 ‑50/250 CABLE 6 m PCK).
9